FCU Hookup Kit

HerzCON

Direct connection for fan coils in heating and cooling systems

HerzCON from HERZ Armaturen is a preassembled connection unit for fan coil units. It combines pressure-independent control, balancing, isolation, filtration, flushing and draining in one compact unit.

Manufactured byHERZ Armaturen
HERZ Armaturen logo
HerzCON direct connection unit for fan coil units by HERZ Armaturen
HerzCON FCU hookup kit from HERZ Armaturen.
Overview

One preassembled unit for each fan coil

HerzCON is a direct connection unit for fan coils in heating and cooling systems. Control, balancing, isolation, filtration, flushing and draining are combined in one unit that is fully assembled and tested in the factory.

At its core is the HERZ 4006 SMART pressure-independent balancing and control valve (PIBCV). Multifunctional ball valves, a strainer with drain valve and a flushing bypass allow the circuit to be filled, drained, flushed and cleaned through the unit.

Components

What is inside the unit

Exploded view of the HERZ HerzCON unit: PIBCV, multifunctional ball valves, strainer with drain valve and insulation box
Exploded view of the HerzCON unit and insulation box.

4006 SMART PIBCV

Pressure-independent balancing and control valve. Keeps the flow constant when the system pressure changes; flow is preset in percent.

Multifunctional ball valves

Supply and return isolation with red and blue handles. The full-bore T-port allows draining or filling of the system.

Strainer with drain valve

HERZ strainer with 2512 blow-down drain valve, for flushing and cleaning the strainer basket in place.

Flushing bypass

Bypass for flushing the pipework with the fan coil isolated, as recommended by BSRIA BG29/2011.

Venting valve and test points

Venting valve and 0284 test points for flow and differential-pressure measurement.

Insulation box

For DN15 to DN25, standard or FR1 version. Vapour-impermeable and supplied vapour sealed for chilled water.

Sizes

Sizes and flow data

SizeKvs normal
m³/h
Kvs bypass
m³/h
Flow @100%
l/h
Flow @100%
l/s
Max. Δp
bar
DN15 LF0.204.81200.0334
DN15 MF0.344.81900.0534
DN15 SF1.654.88000.2226
DN15 HF2.544.812000.3336
DN20 SF2.465.412000.3336
DN20 HF3.335.420000.5566
DN252.751019000.5284
DN324.5714.225000.6944

Values from the HERZ HerzCON datasheet. Recommended presetting: 20% to 80% of nominal flow. Pipe centres: 65 mm (DN15, DN20), 90 mm (DN25), 100 mm (DN32).

Operating Modes

Four operating modes in one unit

HerzCON normal operation – flow path and valve positions

Normal operation

Bypass and strainer drain closed; the PIBCV is preset to the design flow.

HerzCON bypass flushing – flow path and valve positions

Bypass flushing

Bypass open and PIBCV closed, so the pipework is flushed without passing through the fan coil.

HerzCON forward flushing – flow path and valve positions

Forward flushing

Supply ball valve and strainer drain open; flushing through the strainer to atmosphere.

HerzCON backflushing – flow path and valve positions

Backflushing

Strainer drain and PIBCV open; flushing through the ball valve, PIBCV, fan coil and strainer.

Applications

Where HerzCON is used

Application diagram of HERZ HerzCON units connecting fan coils on heating and cooling risers
HerzCON units at each fan coil on heating and cooling risers.

Fan coil units

Direct connection of fan coils with control, balancing and flushing in one unit.

Chilled water circuits

Vapour-sealed insulation box for cooling duty, DN15 to DN25.

Heating circuits

Hot water operation up to 130 °C.

Hydronic networks

Commercial, institutional and residential buildings.

Features

Technical data

Pressure & temperature

  • Max. operating pressure: 25 bar.
  • Operating temperature: -20 °C to 130 °C.
  • Max. differential pressure: 4 or 6 bar, depending on size.
  • Valve lift: 4 mm.

Control & balancing

  • Flow preset in percent on the valve; recommended 20% to 80% of nominal flow.
  • Actuators: 7708 two-point, 7711 two-point or pulse, 7990 continuous control.
  • On/off or modulating 0–10 V DC actuators; BMS integration possible.
  • Test points P1–P2 for flow; DN15 SF/HF and DN20 SF/HF add P3 for minimum Δp.

Materials & media

  • Body: dezincification-resistant (DZR) brass.
  • Membranes and O-rings: EPDM.
  • Water to ÖNORM H 5195-1; water quality to ÖNORM H 5195 and VDI 2035.
  • Ethylene or propylene glycol, 25 to 50 vol.%. Mineral-oil lubricants can damage EPDM seals.

Insulation box fire behaviour

  • Standard box: Class E (DIN EN ISO 11925-2), B2 (DIN 4102-1).
  • FR1 box: Classes B, C, D (DIN EN ISO 11925-2), B1 (DIN 4102-1).
Benefits

Why choose HerzCON

One unit, fewer joints. Assembled and tested in the factory, so fewer fittings are made on site.
Stable flow at each fan coil. Pressure-independent control keeps the design flow when the system pressure changes.
Simpler commissioning. Percent presetting and test points make flow setting and checking quicker.
Clean circuits. The flushing bypass and in-place strainer cleaning keep dirt out of the fan coil.
Heating and chilled water. The vapour-sealed insulation box makes the same unit suitable for cooling.
Easy maintenance. Isolation, draining and strainer cleaning without removing the unit.

Need support with HerzCON?

Share the fan coil flow rate, pipe size and whether the circuit is heating or chilled water, and our MEP team will support you with the suitable HerzCON size.